Fire Alarm Testing: Weekly, Six-Monthly and Annual Checks
What BS 5839-1 expects from weekly call point tests and six-monthly servicing, and how to make sure every device is tested each year.
4 min read
NICEIC, Gas Safe and Refcom
Photos and certificates on every job
Written by our building services team
A commercial fire alarm should be tested by the building’s own staff every week and inspected and serviced by a competent engineer at least every six months. Across each year, every detector, call point and sounder should be tested at least once. That is the pattern BS 5839-1 sets out, and it is what fire risk assessors, insurers and fire officers will check against.
Like emergency lighting, a fire alarm spends almost all of its life doing nothing. Regular testing is the only way to know it will work on the day it is needed.
Who is responsible?
Under the Regulatory Reform (Fire Safety) Order 2005, the Responsible Person for a non-domestic building must make sure fire detection and warning systems are maintained in good working order. In practice that usually means the employer, the building owner or the managing agent, and on many estates it is a duty passed to an FM provider under contract.
BS 5839-1 is the code of practice for fire detection and alarm systems in non-domestic buildings. It is not law, but it is the benchmark used to judge whether a system has been looked after properly.
Weekly test
Once a week, someone on site should set off the alarm from a manual call point (the red break-glass box on the wall) and check that the panel receives the signal and the sounders operate. Good practice is to:
Use a different call point each week, working round the building so every one is tested in rotation
Test at roughly the same time each week, so occupants know it is a test
Keep the test short, and record it in the log book with the call point used
The weekly test is a user check, not a service. It proves the basic chain from call point to panel to sounders still works.
Six-monthly inspection and servicing
BS 5839-1 recommends that a competent person inspects and services the system at intervals of no more than six months. Your fire risk assessment may call for more frequent visits in higher-risk buildings. A typical service visit covers:
Checking the log book and following up any faults or false alarms since the last visit
Inspecting the control panel, power supplies and standby batteries
Testing a sample of detectors, call points and sounders, plus any interfaces such as door holders, lift recall, ventilation shutdown or links to an alarm receiving centre
Checking that changes to the building, such as new partitions or a change of use, have not left areas uncovered
Issuing a servicing certificate
Making sure every device is tested each year
Over any 12-month period, every device on the system should be functionally tested. Most service contracts split the devices across the two six-monthly visits so that each one is covered once a year. Detectors should be tested with the right test equipment, such as smoke, heat or multi-sensor testers, not just by checking the panel.
If your annual records cannot show that every device was tested, that is a gap a fire risk assessor is likely to pick up.
Keep the log book
Every weekly test, service visit, fault, false alarm and repair should be recorded. A complete log book is one of the first things a fire officer or auditor will ask to see, and it is also the best evidence you have that the system has been maintained.
Common problems we find
Weekly tests that use the same call point every time, so others go untested for years
Detectors painted over, covered or removed during fit-outs
Standby batteries past their service life
Rooms added or reconfigured without any change to detection
Repeated false alarms from detectors in the wrong place, such as smoke detectors near kitchens or showers
Fire doors held open on magnetic holders that no longer release when the alarm sounds
That last point is where the alarm system meets passive fire protection. Detection and alarm warn people; fire doors and fire stopping hold the fire back while they leave. Both need to be maintained.
How TECS can help
We service and maintain fire alarm systems for schools, offices, public buildings and FM providers across London, the Home Counties, East Anglia and the East Midlands. We can take on the six-monthly servicing as part of a planned maintenance programme alongside emergency lighting testing and other statutory checks, or pick up overdue fire alarm visits for FM providers with a backlog through our FM partner support.
Find out more about our fire alarm servicing, or Enquire Now to book a service or a survey of your system.
Need help?
Talk to a building services specialist.
Mechanical, electrical, fire and security services for commercial buildings. Tell us about your building and we’ll recommend the right services.
Or call 0800 368 9954, Mon–Fri 8am–5pm
Explore
Keep reading