Commercial boiler plant in a plant room

Insights

/

Mechanical

Getting Commercial Heating Ready for Winter

The checks that stop boilers, pumps and controls failing in the first cold week, and what to ask your contractor for.

4 min read

NICEIC, Gas Safe and Refcom

Photos and certificates on every job

Written by our building services team

Most commercial heating failures happen in the first cold week of the heating season, when systems that have sat idle all summer are suddenly asked to run flat out. A short programme of checks in October and November catches most of these faults before they turn into complaints, closed rooms or an emergency call-out.

Here is what a good pre-winter heating check covers, and what facilities managers should ask their contractor for.

Start with the annual service

Every gas-fired boiler and burner should have an annual service by a Gas Safe registered engineer. For commercial plant, that service should include:

  • Combustion analysis, with flue gas readings recorded against the manufacturer’s figures

  • Cleaning of heat exchangers, burners and condensate traps

  • Checks on flame supervision, safety controls and gas pressures

  • A flue inspection, including terminals that may have been blocked over the summer

  • A Gas Safety Record for the plant, kept with your building records

If your boilers were last serviced in spring, they may not need a full service again. They do need a recommissioning check before the heating season, because pumps seize, valves stick and controls drift when a system has been off for months.

Check the whole system, not just the boiler

A boiler that fires perfectly is no use if the heat never reaches the room. Ask for checks on the rest of the system too:

  • Pumps: run each one, check for noise and leaks, and swap duty and standby pumps so both get used

  • Pressurisation units: check the system pressure, the expansion vessel charge and the low-pressure cut-out

  • Valves: exercise isolating and motorised valves so they don’t stick when they’re needed

  • Radiators and fan coils: bleed air, check thermostatic valves and clean filters on fan coil units

  • Pipework: look for leaks, missing insulation and signs of corrosion in plant rooms and risers

Get the controls right

Many heating complaints are controls problems, not plant problems. Time clocks still on summer hours, frost thermostats set too low and sensors that have drifted all cause cold buildings and wasted energy.

If your building has a BMS, check that heating schedules match how the building is used this winter, not how it was used two years ago. Occupancy changes, hybrid working and new tenants all mean old schedules can be wrong. Optimum start, weather compensation and frost protection should all be tested, not just assumed to work.

Plan for the cold snap

Even well-maintained plant can fail. A little planning keeps a fault from becoming a crisis:

  • Know where your critical spares are, such as pump seals, ignition leads and the controls boards most likely to fail

  • Make sure your contractor has up-to-date plant records, so the engineer arrives with the right parts

  • Agree in advance what happens if a boiler fails, and whether temporary heating is needed for critical areas

  • Protect plant and pipework in unheated spaces, such as roof plant rooms, car parks and loading bays, against frost

Don’t forget hot water

Winter checks are a good time to look at domestic hot water too. Calorifiers and water heaters should store water at 60°C and distribute it at 50°C or above to control Legionella. Low temperatures in winter often point to a failing heater, a pump fault or a poorly balanced return. Thermostatic mixing valves should be serviced to your water hygiene schedule.

Keep the records

After the checks, you should have a clear record of what was done: service reports, combustion readings, Gas Safety Records and a list of any defects with recommended fixes. If you manage several sites, ask for the defects to be ranked by risk so you can spend the budget where it matters.

Good records also make next winter easier. Faults that repeat year after year usually mean a part needs replacing, not repairing again.

How TECS can help

TECS services and repairs commercial heating plant across London, the Home Counties, East Anglia and the East Midlands, both for building owners and as a contractor to FM providers. Our Gas Safe engineers carry out boiler servicing, recommissioning, controls checks and repairs, with every visit logged through our helpdesk.

To book pre-winter heating checks for your buildings, Enquire Now.

Need help?

Talk to a building services specialist.

Mechanical, electrical, fire and security services for commercial buildings. Tell us about your building and we’ll recommend the right services.

Or call 0800 368 9954, Mon–Fri 8am–5pm

Keep reading

More building services insights.

Practical guidance on building services maintenance, compliance and keeping buildings running.

Practical guidance on building services maintenance, compliance and keeping buildings running.

TECS helpdesk team member taking a call

Let’s keep your
building running.

Get in touch with our helpdesk about planned maintenance, repairs, compliance testing or a project.